Pressure leak detector gas (DLG) with 450 mbar alarm pressure for above and underground double-walled tanks with 600 mbar minimum test pressure of the interstitial space
with digital manometer (M)
with service indication (Si) indicates the due and prescribed functional test depending on the set maintenance/service interval (time period adjustable between 1 and 63 months)
For the monitoring of water-polluting liquids of those the (possible) explosive vapor-air mixtures (also such ones that can arise through the stored/conveyed liquids in contact with air, humidity, condensation or the materials used) must be classifiable into gas group II A to II B3 as well as in the temperature code T1 to T3, for example: petrol.
power supply: 100-240 VAC | 24 VDC
plastic box (pl-box)
IP rate: IP30
temperature range: -0 °C .. +40 °C (indoor installation)
pneumatic connection: stainless steel compression ferrule SS-CF8/6 for stainless steel (ss) pipe 8/6x1mm or polyamide (PA) hose 8/6x1mm with support sleeve
supply connection: compression ferrule CF6/4 for copper (CU) pipe 6/4x1mm