VL 570

VL 570
 
For increasing, move mouse over the picture
Vacuum leak detector for double-walled horizontal cylindrical containments, tanks, sumps, etc.

TYPES:
VL 570

OPTIONAL EQUIPMENT:
P: weatherproof housing
M: digital manometer
S: service display (preset to 12 months)
Si: service indication (adjustable 1 to 63 months)
LE: remote monitoring LOD with Ethernet module
(eg. VL 570 M)

TANKS:
  • Maximum liquid pressure on tank bottom: <= 540 mbar
  • Maximum internal overlay pressure: 500 mbar
  • Underpressure resistance of interstitial space: up to -900 mbar

STORED PRODUCTS:
Water-polluting liquids with a flash point > 60 °C (for Germany > 55 °C acc. TRBS and TRGS) where no explosive vapor-air mixtures occur.

INSTALLATION:
Outside Ex areas

HOUSING / IP RATE / TEMPERATURE RANGE:
pl-box: plastic box / IP 30 / -0 °C .. +40 °C
ss-box: stainless steel box / IP 54 / -40 °C .. +60 °C

PNEUMATIC CONNECTIONS:
H4+H6: hose connection for polyvinylchloride (PVC) hose 8/4x2mm or 10/6x2mm (only for pressureless tanks)
QU8/6: quick union for polyamide (PA) hose 8/6x1mm (for tanks with up to 500 mbar overpressure)
CF8/6: compression ferrule for copper (CU) pipe 8/6x1mm or polyamide (PA) hose 8/6x1mm (for tanks with up to 500 mbar overpressure)
PP8/6: polypropylene connection for polyamide (PA) hose 8/6x1mm or polytetrafluoroethylene (PTFE) hose 8/6x1mm (for tanks with up to 500 mbar overpressure)

The requirements of the respective documentation must be observed!