Vacuum leak detector explosion protected electronically operating (VLXE ..), partially explosion protected with integrated pump, for the installation outside of Ex-areas, weatherproof design,
with 34 mbar alarm pressure
with detonation flame arresters in suction and exhaust line
for one above or underground double-walled tank with suction line to the low point of the interstitial space
with digital manometer (M)
with service indication (Si) indicates the due and prescribed functional test depending on the set maintenance/service interval (time period adjustable between 1 and 63 months)
for the monitoring of water-polluting liquids II A to II B3 as well as in the temperature code T1 to T3, for example: petrol and ethanol-containing fuels, diesel, kerosene, etc.
Vapors must be heavier than air!
If the flash point of the liquid to be monitored requires explosion protection measures, the VLXE .. M can only be used on pressureless tanks.
Otherwise the VLXE .. M can also be used on tanks or pipes with up to 5 bar overpressure.
The international hazardous substances law sets a limit of > 60 °C. National regulations may vary, so in Germany > 55 °C.
power supply: 100-240 VAC | 24 VDC
stainless steel box (ss-box)
IP rate: IP66
temperature range: -40 °C .. +60 °C
pneumatic connection: compression ferrule CF8/6 for copper (CU) pipe 8/6x1mm or polyamide (PA) hose 8/6x1mm with support sleeve