Pressure leak detector pipeline pump (DLR-P) with 2,0 bar alarm pressure for above and underground double-walled pipes and 3,0 bar minimum test pressure of the interstitial space
with weatherproof design (P)
with digital manometer (M)
with service indication (Si) indicates the due and prescribed functional test depending on the set maintenance/service interval (time period adjustable between 1 and 63 months)
with pulsation damper (pul-d)
for the monitoring of water-polluting liquids whose (possible) explosive vapor-air mixtures (also such ones that can arise through the stored/conveyed liquids in contact with air, humidity, condensation or the materials used) can be classified into gas group II A to II B3 as well as in the temperature code T1 to T3, for example: petrol.
power supply: 100-240 VAC | 24 VDC
stainless steel box (ss-box)
IP rate: IP66
temperature range: -40 °C .. +60 °C
pneumatic connection: compression ferrule CF8/6 for copper (CU) pipe 8/6x1mm or polyamide (PA) hose 8/6x1mm with support sleeve