Vacuum leak detector explosion protected electronically operating (VLXE ..), partially explosion protected with integrated pump, for the installation outside of Ex-areas, weatherproof design,

with 330 mbar alarm pressure

with detonation flame arresters in suction and exhaust line

for one above or underground double-walled tank or for above and underground double-walled pipes

with digital manometer (M)

stainless steel version (ss-v): screw connection, valves and internal piping made from stainless steel

for the monitoring of water-polluting liquids of those the (possible) explosive vapor-air mixtures (also such ones that can arise through the stored/conveyed liquids in contact with air, humidity, condensation or the materials used) must be classifiable into gas group II A to II B3 as well as in the temperature code T1 to T3, for example: petrol and ethanol-containing fuels, diesel, kerosene, etc.

Vapors must be heavier than air!

If the flash point of the liquid to be monitored requires explosion protection measures, the VLXE .. M can only be used on pressureless tanks.

Otherwise the VLXE .. M can also be used on tanks or pipes with up to 5 bar overpressure.

The international hazardous substances law sets a limit of > 60 °C. National regulations may vary, so in Germany > 55 °C.

power supply: 100-240 VAC | 24 VDC

stainless steel box (ss-box)

IP rate: IP66

temperature range: -40 °C .. +60 °C

pneumatic connection: stainless steel flared union ss-FU6/4 for stainless steel (ss) pipe 6/4x1mm